Motor will not start or the overload keeps tripping

Manual section
Book 8 · § 4.4 · 5 · 6 · 14.1
Level
TECHNICIAN
SUPPLY MCC PANEL VSD MOTOR SENSOR E-STOP

Symptom

A motor does not start, hums without turning, trips at start or after running, runs hot, or a drive shows an overcurrent or overtemperature fault.

Likely causes

  1. An E-stop, interlock or control fuse is open, so the contactor never pulls in.
  2. One phase missing, or low or unbalanced supply voltage.
  3. The machine is jammed or starting loaded (mixer with a trapped batch, screw full of cement).
  4. Overload relay set below the motor nameplate, or a contactor with burnt contacts.
  5. Dirt on the motor fins, a failed drive fan, or a hot cabinet.

Most likely and cheapest to check first.

Checks

  1. Read the alarm and the PLC output lamp; check the safety relay status.
  2. Have an electrician measure all three phases and the running current on each.
  3. Lock out and turn the driven machine by hand.
  4. Compare the overload setting with the nameplate full-load current.

Fix

  1. Find and fix the open interlock; never bridge it.
  2. Restore the missing phase; correct the supply.
  3. Empty and free the machine before restarting.
  4. Set the overload to the nameplate, never higher; replace worn contactors with the same type and coil voltage.
  5. Clean motor fins and drive heatsinks; replace failed fans.

Stop the equipment if

The breaker trips instantly, or a motor hums without turning. Do not keep resetting it.

Parts you may need

A tripping overload is telling you something

Raising the overload setting to stop nuisance trips burns motors. First look for the mechanical cause - a seized bearing, build-up, a slipping belt, a trapped batch.

DANGERElectrical work is for qualified electricians, with the circuit isolated and tested dead. Operators read indicators, do visual checks and report faults clearly.
FIELD TIPThermograph the panels during a busy production morning. A panel scanned with the plant idle always looks perfect.

⚠ Every check inside a machine starts with full lockout. Safety disclaimer